Installation and Operation Manual
FW6000 Fire Alarm Control Panel
FW6000 Intelligent Fire Alarm Control Panel (FACP) is the new-generation fire alarm control unit designed by our company for applications in small and medium projects. It is wall-mounted type and has the advantages of powerful function, high reliability and flexible configuration. The panel is equipped with a LCD monitor to display all the information on fire alarms, faults and various operations, which can be printed out by the built-in printer. FW6000 is a one-loop control panel with maximum 240 points, which can work together with all FW 3 series field devices.
Note: COM port needs grounding
1,(Monitoring Start Output)HJ: Active NO terminal to Fire alarm routing device (use jumper to switch
between passive and active), which will close to connect +24V output after started (each points with a
max output current of 100mA)
2,(Monitoring Start Output)SG: Active NO terminal to Sounder Strobe (Both active and passive modes,
use jumper to switch between passive and active), which will close to connect +24V output after
started (with max output current of 100mA for each direct-start point)
3,BUS: Non-polarity two-wire bus terminal
4,Linkage power supply output: 24VDC(Max output current 1A)
5,Main board power supply input: 220VAC
6,Grounding Terminal: Grounding
FW6000 Fire Alarm Control Panel
FW6000 Intelligent Fire Alarm Control Panel (FACP) is the new-generation fire alarm control unit designed by our company for applications in small and medium projects. It is wall-mounted type and has the advantages of powerful function, high reliability and flexible configuration. The panel is equipped with a LCD monitor to display all the information on fire alarms, faults and various operations, which can be printed out by the built-in printer. FW6000 is a one-loop control panel with maximum 240 points, which can work together with all FW 3 series field devices.
Note: COM port needs grounding
1,(Monitoring Start Output)HJ: Active NO terminal to Fire alarm routing device (use jumper to switch
between passive and active), which will close to connect +24V output after started (each points with a
max output current of 100mA)
2,(Monitoring Start Output)SG: Active NO terminal to Sounder Strobe (Both active and passive modes,
use jumper to switch between passive and active), which will close to connect +24V output after
started (with max output current of 100mA for each direct-start point)
3,BUS: Non-polarity two-wire bus terminal
4,Linkage power supply output: 24VDC(Max output current 1A)
5,Main board power supply input: 220VAC
6,Grounding Terminal: Grounding

2.4 Technical Specifications 2.4.1 Power Supply: AC power: Nominal operation voltage 220VAC (187VAC ~ 242VAC) Standby Battery: 2 x 12V/12AH 2.4.2 Operating Environment: Temperature: 0ºC~+40ºC Relative Humidity: ≤95%, non-condensing 2.4.3 Capacity: One loop with maximum 240 devices 2.4.4 Display: LCD 128×64 lattice graphic 2.4.5 Dimension: (Length ×Width ×Height):330.0mm×130.0mm×400.0mm 2.4.6 Wiring requirement 1,Recommend to use RVS2×1.0MM2 or RVS2×1.5MM twisted wire for CAN communication wire and bus wire, while use RVSP2×1.0mm2 at the high interference environment. 2,Not allowed to lay CAN communication wire and telephone line together with bus wire inside the same multi-core cable. |